摘要
随着国民经济的快速发展,工业化进程和城镇化建设步伐不断加快,电力的需求量也不断增长。电网的供电能力和可靠性,对工业区的生产和运作是极为重要的。本论文中主要是电气一次部分的设计说明,其内容包括:变电所电气主接线设计,负荷计算,主接线方案确定,短路电流计算,主要电气设备选型,变电所电气总平面布置及继电保护的配置。设计中还对主要高压电器设备进行了选择与计算,如断路器、隔离开关、电压互感器、电流互感器等。此外还进行了防雷保护的设计和计算,提高了整个变电所的安全性。
关键词:综合自动化二次回路短路电流接地保护
AutomotiveDesign Area with 220kV Substation Buck
Abstract
Withthe rapid development of the national economy, the process ofindustrialization and urbanization continues to accelerate the paceof construction, the demand for electricity is also growing. Thepower supply capacity and reliability of the grid, and the operationof the industrial production area is extremely important. This paperis mainly a description of the design of electrical parts, itscontents include: the main substation electrical wiring design; loadcalculation; Main Wiring OK; short-circuit current calculation; mainelectrical equipment selection; electrical substation general layout;configuration protection. Design is also on the main
disconnectors, voltage transformers, current transformers. It alsoconducted a lightning protection design and calculation, improves thesecurity of the entire
high-voltage electrical equipmentselection and calculation, such as circuit breakers,
substation.
Keywords: integrated automation groundfault
secondarycircuit short-circuit current
目 录
摘要...........................................................................................................................IAbstract..........................................................................................................................II第1章绪论...................................................................................................................11.1国内外现状和发展趋势.................................................................................11.2原始资料.........................................................................................................31 3设计内容及要求.............................................................................................3第2章电气主接线的设计..........................................................................................42.1电气主接线设计概述......................................................................................42.1.1对电气主接线的基本要求..................................................................4
2.1.2变电所电气主接线的设计原则..........................................................4
2.1.3电气主接线的设计步骤......................................................................5
2.2主接线的基本接线形式及其特点.................................................................6
2.3电气主接线的选择.........................................................................................8 2.2.1电气主接线分类..................................................................................6
3.1.2主变压器容量的选择........................................................................12
3.2主变压器型式的选择...................................................................................14
3.2.1主变压器相数的的选择....................................................................14
3.2.2绕组数量和连接方式的选择............................................................15
3.3主变压器的选择结果...................................................................................15
3.4无功补偿.......................................................................................................15
3.4.1无功补偿的目的................................................................................15
3.4.2无功功率的人工补偿装置................................................................16
3.4.3并联电容器的选择计算....................................................................16
第4章短路电流计算................................................................................................17
4.1短路电流计算概述.......................................................................................17
4.1.1短路电流计算的目的.........................................................................17
4.1.2短路电流计算的方法和步骤............................................................17
4.2变压器的各绕组电抗标幺值计算...............................................................19
4.2.1基准值计算......................................................................................19
4.2.2各元件参数标幺值计算..................................................................20
4.3220KV侧短路计算.......................................................................................204.4 110KV侧短路计算.......................................................................................204.5 35KV侧短路计算........................................................................................20第5章一次设备的选择与校验...............................................................................225.1断路器和隔离开关的选择...........................................................................225.1.1断路器的选择..................................................................................22
5.1.2隔离开关的选择..............................................................................25
5.2导体的选择与校验.......................................................................................28第6章二次接线设计................................................................................................326.1变电所操作电源选择...................................................................................326.2中央信号装置的选择...................................................................................336.2.1中央信号装置的设计原则...............................................................33
6.2.2闪光装置..........................................................................................33
6.3.1设计原则..........................................................................................33 6.3.2变压器的电压回路与电流回路......................................................34
6.3断路器的控制、信号回路的选择...............................................................33
7.1.2变电站防入侵雷保护......................................................................39
7.1.3避雷器的选择..................................................................................40
7.1.4变压器的防雷保护..........................................................................42
7.1.5内部过电压及其保护......................................................................43
7.2 接地装置设计.............................................................................................43
7.2.1接地简介..........................................................................................43
7.2.2接地网型式选择..............................................................................44
第8章总结................................................................................................................45
参考文献......................................................................................................................46
致谢..............................................................................................................................48
第1章绪论
1.1国内外现状和发展趋势
(1)数字化变电站技术发展现状和趋势
以往制约数字化变电站发展的主要是IEC61850的应用不成熟,智能化一次设备技术不成熟,网络安全性存在一定隐患。但2005年国网通信中心组织的IEC61850互操作试验极大推动了IEC61850在数字化变电站中的研究与应用。目前IEC61850技术在变电站层和间隔层的技术已经成熟,间隔层与过程层通信的技术在大量运行站积累的基础上正逐渐成熟[1]。
(2)当前的变电站自动化技术
20世纪末到21世纪初,由于半导体芯片技术、通信技术以及计算机技术飞速发展,变电站自动化技术也已从早期、中期发展到当前的变电站自动化技术阶
次,
而是以间隔和元件作为设计依据,即变电站层和间隔层,在设计理念上不是以整个变电站作为所要面对的目标,在中低压系统采用物理结构和电器特性完全独段。其重要特点是:以分层分布结构取代了传统的集中式;把变电站分为两个层
的间隔出线,立,
量内存、闪存以及电子固态盘和嵌入式软件系统;现场总线以及光纤通信的应用为功能上的分布和地理上的分散提供了技术基础;网络尤其是基于TCP/IP的以太网在变电站自动化系统中得到应用;智能电子设备(IED)的大量应用,诸如继电保护装置、自动装置、电源、五防、电子电度表等可视为IED而纳入一个 与继电保护、各种IED、远方调度中心交换数据所统一的变电站自动化系统中
;使用的规约逐渐与国际接轨。这个时期国内代表产品有CSC系列、NSC系列及BSJ系列[2]。
(3)国外变电站自动化技术
国外变电站自动化技术是从20世纪80年代开始的,以西门子公司为例,该公司第一套全分散式变电站自动化系统LSA678早在1985 年就在德国汉诺威正式投入运行,至1993年初,已有300多套系统在德国和欧洲的各种电压等级的变电站运行。在中国,1995年亦投运了该公司的LSA678变电站自动化系统。LSA678的系统结构有两类,一类是全分散式,另一类是集中和分散相结合,两
类系统均由6MB测控系统、7S/7U保护系统、8TK开关闭锁系统三部分构成[3]。
(4)原始变电站自动化系统存在的问题
资料分目前国际上关于变电站自动化系统和通讯网络的国际标准还没有正
式公布,国内也没有相应的技术标准出台。标准和规范的出台远落后于技术的发
展,导致变电站自动化系统在通讯网络的选择、通讯传输协议的采用方面存在很
大的争议,在继电保护和变电站自动化的关系及变电站自动化的概念上还存在分
歧。市场竞争日益激烈,不同厂家的设备质量和技术(软硬件方面)差异甚大,
各地方电力公司的要求也不尽相同,导致目前国内变电站自动化技术千差万别。
改革开放以来,随着我国国民经济的快速增长,电力系统也获得了前所未有的发
展,电网结构越来越复杂,各级调度中心需要获得更多的信息以准确掌握电网和
变电站的运行状况。同时,为了提高电力系统的可控性,要求更多地采用远方集
中监视和控制,并逐步采用无人值班管理模式。显然传统的变电站已经远远不能
满足现代电力系统管理模式的需求。
传统变电站一般采用常规设备,二次设备中的继电保护和自动装置、远动装置等
采用电磁式或晶体管式,体积大,设备笨重,主控室、继电保护室占地面积大。
方法已经被国内外摒弃和淘汰。
势[4]。 采用一种更先进的技术改造变电站是一种必然趋常规装置结构复杂,可靠性低,维护工作量大。因此,传统变电站的设计思路和
何谓变电站综合自动化呢?它是指利用先进的计算机技术、现代电子技术、通信
技术和信号处理技术,实现对变电站主要设备和传、配电线路的自动监视、测量、
控制、保护以及与调度通信等综合性自动化功能。其重要特点是:以分层分布结
构取代了传统的集中式;把变电站分为两个层次,即变电站层和间隔层,在设计
理念上不是以整个变电站作为所要面对的目标,而是以间隔和元件作为设计依据
[5]。
我国对变电站的技术研究的其中一个主要方面是在220kV及以下中低压变
电站中采用综合自动化技术,全面提高变电站的技术水平和运行管理水平,而且
技术不断得到完善和成熟。总体来说,实现变电站综合自动化,其优越性主要有:
提高了供电质量、变电站的安全可靠运行水平,降低造价,减少了投资,促进了
无人值班变电站管理模式的实行[6]。
本设计中变电站的设计思路是紧跟现代化国内外变电站综合自动化技术的
发展趋势,根据最新和最权威的设计规程和规范,采用先进的原理技术,摒弃落
后和即将淘汰的技术,确定科学的模式和结构,选择质量优良和性能可靠的产品,
因此,在学习借鉴国外先进技术的同时,结合我国的实际情况,全面系统地研究
探讨符合国情的变电站系统设计模式,完成本次毕业设计。
1.2原始资料
变电所规模及性质:汽车工业区变电所
电压等级220kV/110KV/35KV
绞线回数220KV 2回交联电缆(发展1回)
110KV 4回电缆回路(发展6回)
35KV 30回电缆回路,一次性配备。
最大负荷利用小 6500小时
1.3设计内容及要求
根据所给原始资料,进行负荷计算,主接线方案确定,主变压器选择,短路
电流计算及一次设备选择检验,变电站进出绞及电源联络选择,二次回路方案和
继电保护、防雷保护、接地保护设计等。
第2章电气主接线的设计
变电所的电气主接线是指由发电机、变压器、断路器、隔离开关、互感器、母线和电缆等电气设备,按照一定的顺序连接的,用以表示生产、汇集和分配电能的电路。电气主接线又称一次接线或电气主系统,代表了发电厂和变电所电气部分的主体结构,直接影响着配电装置的布置、继电器保护配置、自动装置和控制方式的选择,对运行的可靠性、灵活性和经济性起决定性作用。
2.1电气主接线设计概述
2.1.1对电气主接线的基本要求
电气主接线的基本要求:
(1)电气主接线应根据系统和用户的要求,保证供电的可靠性和电能质量。
个独立电源供电,供电。 其中任一电源必须在另一电源停止供电时, 能保证向重要负荷对三类负荷以一个电源供电即可。对一类负荷和二类负荷占大多数的用户应由两
状态。不仅要求在正常运行时能安全可靠地供电,而且在系统故障或设备检修及
故障时,也能适应调度的要求,并能灵活、简便、迅速地倒换运行方式,使停电
时间最短,影响范围最小。
(3)电气主接线应在满足上述要求的前提下,尽可能经济。应尽量减少设备投资费用和运行费用,并尽量减少占地面积,同时注意搬迁费用、安装费用和外汇费用。
(4)具有发展和扩建的可能性。电气主接线在设计时应尽量留有发展余地,不仅要考虑最终接线的实现,同时还要兼顾到从初期接线过渡到最终接线的可能和分阶段施工的可行方案,使其尽可能的不影响连续供电或在停电时间最短的情况下完成过渡方案的实施。
2.1.2变电所电气主接线的设计原则
变电所主接线的设计必须满足上述四个基本要求,以设计任务书为依据,以国家经济建设方针、政策及有关技术规范为准则,结合工程具体特点,准确地掌
握基础资料,做到既要技术先进,又要经济实用。
我国《变电所设计技术规程》对主接线设计作了如下规定:
在满足运行要求时,变电所高压侧应尽量采用断路器较少的或不用断路器的接线。在110~220kv变电所中,当出现为2回时,一般采用桥型接线;当出线不超过4回时,一般采用单母线分段接线;当枢纽变电所的出线在4回及以上时,一般采用双母线。在35kv变电所中,当出线为2回时,一般采用桥型接线;当出线为2回以上时,一般采用单母线分段或单母线接线。出线回路数和电源数较多的污秽环境中的变电所,可采用双母线接线。在6~10kv变电所中,一般采用单母线接线或单母线分段接线。
旁路设施可按主接线基本形式中所述的情况设置。
2.1.3电气主接线的设计步骤
电气主接线的设计伴随着发电厂或变电所的整体设计,即按照工程基本建设程序,经历可行性研究阶段、初步设计阶段、技术设计阶段和施工设计等四个阶段。在各阶段中随要求、任务的不同,其深度,广度也有所差异,但总的设计思路、方法和步骤相同。
及远景规划容量, ①变电所的情况,包括变电所的类型,在电力系统中的地位和作用,近期 近期和远景与电力系统的连接方式和各级电压中性点接地方式、
(1)对原始资料进行综合分析
测的基础上确定,其准确性直接影响主接线的设计质量。
③环境条件,包括当地的气温、湿度、污秽、覆冰、风向、水文、地质、海拔高度及地震等因素。这些对主接线中电器的选择和配电装置的实施均有影响,必须予以重视;此外,对重型设备的运输,也应充分考虑。
④设备情况。为使所设计的主接线可行,必须对各主要电器的性能、制造能力、供货情况和价格等资料汇集并进行分析比较,保证设计具有先进性、经济性和可行性。
(2) 确定主变压器的容量和台数
变电所主变压器的容量,一般应按5~10年规划负荷来选择,根据城市规划、负荷性质、电网结构等综合考虑确定。对重要变电所,应考虑当1台主变压器停 应满足Ⅰ类及Ⅱ类负荷的运时,其余变压器容量在记及过负荷能力允许时间内,
供电;对一般性变电所,当1台主变压器停运时,其余变压器容量应能满足全部负荷的70%至80%。
变电所主变压器的台数,对于枢纽变电所在中、低压侧已形成环网的情况下,
以设置2台主变压器为宜;对地区性孤立的一次变电所或大型工业专用变电所,
可设3台主变压器,以提高供电可靠性。
(3)主接线方案的拟定与选择
根据设计任务书的要求,在原始资料分析的基础上,根据对电源盒出线回路
数、电压等级、变压器台数、容量以及母线结构等,可拟定出若干个主接线方案。
依据对主接线的基本要求,从技术上论证并淘汰一些明显不合理的方案,最终保
留2~3个技术上相当,又都能满足任务书要求的方案,在进行经济比较。对于
在系统中占有重要地位的大容量变电所的主接线,还应进行可靠性定量分析计算
比较,最终确定出在技术上合理、经济上可行的最终方案。
(4)所用电源的引接
确定所用电源的引接方式。
(5)短路电流计算和主要电气选择
对所选的电气主接线进行短路电流计算,并选择合理的电气设备。
(6)绘制电气主接线图
2.2 主接线的基本接线形式及其特点 对最终确定的主接线,按工程要求绘制工程图。
一、有母线型的电气主接线
1、单母线接线及单母线分段接线
(1)单母线接线
单母线接线供电电源在变电站是变压器或高压进线回路。母线既可保证电源
并列工作,又能使任一条出线都可以从任一个电源获得电能。各出线回路输入功
率不一定相等,应尽可能使负荷均衡地分配在各出线上,以减少功率在母线上的
传输。
单母接线的优点:接线简单清晰、设备少、操作方便、经济性好,并且母线
便于向两端延伸,扩建方便和采用成套配电装置。
缺点:①可靠性差。母线或母线隔离开关检修或故障时,所有回路都要停止
工作,也就成了全厂或全站长期停电。②调度不方便,电源只能并列运行,不能
分列运行,并且线路侧发生短路时,有较大的短路电流。
适用范围:一般只适用于一台发电机或一台主变压器的以下三种情况:
1、6~10kV配电装置的出线回路数不超过5回;
2、35~63kV配电装置的出线回路数不超过3回;
3、110~220kV配电装置的出线回路数不超过两回。
(2)单母分段接线
单母线用分段断路器进行分段,可以提高供电可靠性和灵活性;对重要用户
可以从不同段引出两回馈电线路,由两个电源供电;当一段母线发生故障,分段
断路器自动将用户停电;两段母线同时故障的几率甚小,可以不予考虑。在可靠
性要求不高时,亦可用隔离开关分段,任一母线故障时,将造成两段母线同时停
电,在判别故障后,拉开分段隔离开关,完成即可恢复供电。
单母线分段接线的缺点是当一段母线或母线隔离开关故障或检修时,该段母
线的回路都要在检修期间内停电;当出线为双回路时,常使架空线路出现交叉跨
越;扩建时需向两个方向均衡扩建。
(3)单母线带旁路母线的接线
为了检修出线断路器,但不中断对该出线的供电,可增设旁路母线。当检修
电源回路断路器期间不允许断开电源时,旁路母线还可以与电源回路连接,此时
还需在电源回路加装旁路隔离开关。有了旁路母线,提高了供电的可靠性,但旁
断供电。
2、双母线接线及分段接线
路系统造价昂贵,同时使配电装置运行复杂化,另外检修母线或母线故障期间中
联络,通过母线联络断路器来实现。由于有了两组母线,时运行的可靠性和灵活
性大为提高。
其优点主要有:①检修母线时不影响正常供电;②检修任一组母线隔离开关
时,只需断开此隔离开关所属回路和与此隔离开关相连的该组母线,其他回路均
可通过另一组母线继续运行;③工作母线发生故障后,所有回路能迅速恢复供电;
④检修任一出线断路器时,可用母联断路器代替检修的断路器,回路只需短时停
电;⑤调度灵活;⑥扩建方便等特点。
缺点:①在倒母线的操作过程中,隔离开关作为操作电器,容易发生误操作;
②检修任一回路的断路器或母线故障时,仍将短时停电;③所使用的设备多(母
线隔离开关的数目多),并且使配电装置结构复杂,所以经济性能差。
(2)双母线分段接线
为了缩小母线故障的停电范围,可采用双母线分段接线,用分段断路器将工
作母线分为两段,每段工作母线用各自的母联断路器与备用母线相连,电源和出
线回路均匀地分布在两段工作母线上。这种接线具有单母线分段和双母线的特点,
较双母线接线具有更高的可靠性和灵活性。正常运行时工作母线工作,备用母线
不工作,它是单母线分段接线方式,当一段工作母线发生故障后,在继电保护作
用下,分段断路器先自动跳开,而后将故障段母线所连的电源回路的断路器跳开,
该段母线所连的出线回路停电;随后,将故障段母线所连的电源回路和出线回路
倒至备用母线上,即可恢复供电,这样,只是部分短时停电,而不必短期停电,
仍是单母线分段运行方式。
双母线分段接线主要用于大容量进出线较多的配电装置中,如220KV进出
线达10~14回时,就可采用双母线三分段的接线。在330~500KV的配电装置
中,也有采用双母线四分段的。
(3)双母线带旁路母线的接线
为了不停电检修出线断路器,双母线可以带旁路母线,用旁路断路器替代检
修中的回路断路器工作,使该回路不致停电。这种接线运行操作方便,不影响双
母线正常运行,但多装了一组断路器和隔离开关,增加了投资和配电装置的占地
面积,然而这对于接于旁路母线的线路回数较多,并且对供电可靠性有特殊需要
二、无母线型的电气主接线
无母线型的电气主接线在电源与引出线之间或接线中各元件之间没有母线
的场合是十分必要的。
2、多角形接线没有集中地母线,相当于将单母线用断路器按电源和引出线
的数目分段,且连接成环形的接线。这种接线一般适用于最终规模已确定的
110kV及以上的配电装置中,且以不超过六角形为宜。多角形接线的缺点之一就
是扩建困难,因此,此接线型式亦不适合本设计的要求。
3、单元接线一般适用于只有一台变压器和一回线路时的小容量终端变电所
和小容量的农村变电所,因此,此接线也不适合本设计的要求。
2.3电气主接线的选择
初选:
为满足可靠性、灵活性、方便性、经济型、可扩建性、安全性,根据对原
始资料的分析以及对主接线的认识,现列出以下三种主接线方案。
方案一:220KV、110KV侧双母线带旁路母线接线(母联兼旁路方式),35KV侧
单母线分段接线。
220kV 进出线两回,而当出线达到5个回路以上时,才增设专用的旁路断路
器,出线少于5个回路时,则采用母联兼旁路或旁路兼母联的接线方式。这种接线方式具备供电可靠、调度灵活、扩建方便等特点。
110kV进出线四回,110kV侧出线可向远方大功率负荷用户供电,其他出线可作为一些地区变电所进线。根据条件选择双母接线带旁路母线方式。
35kV进出线三十回,可向重要用户采用双回路供电。选择单母线分段接线方式。
方案主接线图如图2-1所示
方案二:220KV侧双母线带旁路接线(母线兼旁路方式),110KV侧双母接线、35KV
侧单母线带旁路母线接分段接线。
220kV进出线两回,由于本回路为重要负荷停电对其影响很大,因而选用双母带旁路接线方式。与单母线相比,它的优点是供电可靠性大,可以轮流检修母线而不使供电中断,当一组母线故障时,只要将故障母线上的回路倒换到另一组母线,就可迅速恢复供电,另外还具有调度、扩建、检修方便的优点。
110KV侧双母接线、35KV侧单母线带旁路母线接线,检修出线断路器时,可不中断对该出线的供电,提高了供电的可靠性。
主接线如图2-2所示。
图2-2方案二的电气主接线
方案三:220KV侧、110KV侧双母线接线,35KV侧单母线分段接线。
主接线如图2-3所示。
图2-3方案三的电气主接线
现对三种方案列表2-1比较如下。
表2-1 电气主接线方案比较
项目
可靠性 | 灵活性 | 经济性 | 可扩展性 |
方案
方案一:220KV、110KV 220KV及110KV侧均用双母 检修、调 用29台短 各种电压
侧双母带带旁路母线接 带旁接线,故检修母线时不影 试相对 路器,8条 级接线都
响正常供电,35KV侧用单母 灵活; 母线,占便于扩建
线、35KV侧单母线分
分段接线母线故障时,可保证 地较大。和发展。
段接线
正常段母线不间断供电
方案二:220KV侧双母 220KV侧用双母带旁接线, 灵活性 用29台短 扩建方便
线带旁路接线,110KV 110KV侧用双母线接线,检修 较好; 路器,8条
侧双母接线、35KV侧 母线时不影响正常供电, 母线。
单母线带旁路母线分段 35KV侧用单母分段接线母线
接线。 故障时,可保证正常段母线不
方案三:220KV、110KV 220KV 及110KV 侧均用双母用29台短 各种电压 间断供电
段接线母线故障时,可保证正 和发展。
好;
常段母线不间断供电
综合考虑三种电气主接线的可靠性,灵活性和经济性,结合实际情况,确定
第三种方案为设计的最终方案。
第3章主变压器的选择
在发电厂和变电站中,用来向电力系统或用户输送功率的变压器,称为主变
压器;用于两种电压等级之间交换功率的变压器,称为联络变压器;只供本所(厂)
用的变压器,称为站(所)用变压器或自用变压器。本章是对变电站主变压器的
选择。
3.1主变压器台数和容量的确定
3.1.1变电所主变压器台数的确定
主变压器的台数选择原则为:
(1)对大城市郊区的一次变电所,在中、低压侧已构成环网的情况下,变电所
以装设两台主变压器为宜。
(2)对地区性孤立的一次变电所或大型工业专用变电所,在设计时应考虑装设
三台主变压器的可能性。
(3)对于规划只装设两台主变压器的变电所,以便负荷发展时,更换变压器的
容量。
主变压器。
(1)主变压器容量的确定原则
①主变压器容量一般按变电所建成后5~10年的规划负荷选择,并适当考虑到
远期10~20年的负荷发展。对于城郊变电所,主变压器容量应与城市规划相结
合。
②根据变电所所带负荷的性质和电网结构来确定主变压器的容量。对于有重要
负荷的变电所,应考虑当一台主变压器停运时,其余变压器容量在计及过负荷能
力后的允许时间内,应保证用户的一级和二级负荷;对一般性变电所,当一台主
变压器停运时,其余变压器容量应能保证全部负荷的70%~80%。
③同级电压的单台降压变压器容量的级别不宜太多。应从全网出发,推行系列
化、标准化。
(2)本变电所主变压器容量的确定
本设计中该地区的负荷预测情况及发展:2013年负荷为60MW,负荷水平
增长率为10%。设该地区负荷的功率因数为0.9,则2013年该地区负荷视在功率
S | | P | | 60 | | 66 . 67 | ( | MVA ) | |
| | cos | | 0 . 9 | | | | | (3-1) |
根据该地区负荷水平增长率10%,可确定未来5~10年的规划负荷,如2014年
该地区的负荷有功功率:
P | | 60 | | ( 1 | | 10 %) | | 66 ( | MW | ) | (3-2) |
视在功率:
S | | P | | 66 | | 73 . 33 ( | MVA ) | |
| | cos | | 0 . 9 | | | | (3-3) |
2015年该地区的负荷有功功率:
P | | 60 | | ( 1 | | 10 %) | 2 | | 72 . 6 ( | MW | ) | (3-4) |
视在功率:
S | | P | | 72 . 6 | | 80 . 67 | ( | MVA ) | |
| | cos | | 0 . 9 | | | | | (3-5) |
2014年该地区的负荷有功功率:
P | | 60 | | ( 1 | | 10 %) | 3 | | 79 . 86 ( | MW | ) |
视在功率: (3-6) |
视在功率:
S | | P | | 155 . 62 | | 172 . 92 ( | MVA ) | |
| | cos | | 0 . 9 | | | | (3-9) |
该地区未来5~10年的规划负荷情况如表3-1所示。
表3-1该地区未来5~10年的规划负荷情况
年份 | 2013 年 | 2014 年 | 2015 年 | 2016 年 | 2017 年 | 2018 年 |
负荷
P(MW) | 60 | 66 | 72.6 | 79.86 | 87.85 | 96.63 |
S(MV) | 66.67 | 73.33 | 80.67 | 88.73 | 97.61 | 107.37 |
年份
2019 年 | 2020 年 | 2021 年 | 2022 年 | 2023 年 | ― |
负荷
P(MW) 106.29 116.92 128.62 141.48 155.62 ―
S(MVA) 118.11 129.92 142.91 157.20 172.92 ―
根据主变压器容量的确定原则,
证全部负荷的70%~80%,可以确定单台变压器的额定容量。其余变压器容量应能保
2023年变电所单台主变压器的额定容量:sn10=0.7×172.92=121(MVA) (3-12)
综合考虑以上选择原则和本变电所的负荷情况,确定变电所单台主变压器的额定
容量: | s | n | =120MVA 。(3-13) |
3.2主变压器型式的选择
3.2.1主变压器相数的的选择
选择主变压器的相数,需考虑如下原则:
⑴当不受运输条件限制时,在330KV及以下的发电厂和变电站,均应选用三相
变压器。
⑵当发电厂与系统连接的电压为500KV时,已经技术经济比较后,确定选用三
相变压器、两台半容量三相变压器或单相变压器组。对于单机容量为300MW、
并直接升压到500KV的,宜选用三相变压器。
⑶对于500KV变电所,除需考虑运输条件外,尚应根据所供负荷和系统情况,
分析一台(或一组)变压器故障或停电检修时对系统的影响。尤其在建所初期,
若主变压器为一组时,当一台单相变压器故障,会使整组变压器退出,造成全网
停电;如用总容量相同的多台三相变压器,则不会造成所停电。为此要经过经济
论证,来确定选用单相变压器还是三相变压器。
根据以上选择原则以及原始资料分析,本变电站选用三相变压器作为主变压器。
3.2.2绕组数量和连接方式的选择
在具有三种电压等级的变电所中,如通过主变压器各侧的功率均达到该变压
器额定容量的15%以上,或低压侧虽无负荷,但在变电所内需要装设无功补偿设
备时,主变压器一般选用三绕组变压器。
变压器绕组的连接方式必须和系统电压相位一致,否则不能并列运行。电力
系统采用的绕组连接方式只有Y和△,高、中、低三侧绕组如何结合要根据具
体工作来确定。我国110KV及以上电压,变压器绕组多采用Y连接;35KV亦
采用Y连接,其中性点多通过消弧线圈接地。35KV以下电压,变压器绕组多采
用△连接。由于35KV采用Y连接方式,与220、110系统的线电压相位角为0,
这样当变压变比为220/110/35KV,高、中压为自耦连接时,否则就不能与现有
35KV系统并网。因而就出现所谓三个或两个绕组全星接线的变压器,全国投运
绕组变压器,变压器绕组的连接方式为Y/Y/△。本设计中变电所具有三种电压等级,即220kV、110kV和35kV,需选用三
这类变压器约40~50台。
查《电力工程电气设备手册:电气一次部分》,选定变压器的额定容量为
120MVA。这里选择三绕组变压器,所选变压器的技术参数如下所示:
表3-2 220KV三绕组无励磁调压电力变压器
型号 | 额定容量/KVA | 额定电压/KV | 空载电流/% | 空载损耗/KW | 短路损耗/KW | 阻抗电压/% | ||||
高压 | 中压 | 低压 | 高-中 | 高-低 | 中-低 | |||||
SFPS3-120 00/220 | 12000 | 220±(±)* 2.5% | 121 | 38.5 | 1.2 | 163 | 650 | 14.5 | 23 | 7 |
3.4无功补偿
3.4.1无功补偿的目的
变电所中由于有大量的感性负荷,从而使功率因数大大降低。如果在充分
发挥设备潜力、改善设备运行性能、提高其自然功率因数的情况下尚未达到规定
的变电所功率因数时,就需要考虑人工补偿。
3.4.2无功功率的人工补偿装置
进行无功功率人工补偿的设备主要有同步调相机和并联电容器。变电所中普
遍采用并联电容器来补偿供电系统中的无功功率。
并联电容器的补偿方式,有以下三种:
(1)高压集中补偿:将高压电容器组集中装设在变电所的6~10KV母线补
偿方式只能补偿6~10KV母线前所有线路上的无功功率。
(2)低压集中补偿:将低压电容器组集中装设在车间变电所的低压母线上。
这种补偿方式能补偿变电所低压母线前的变压器和所有有关高压系统的无功功
率。
(3)个别就地补偿:将并联电容器组装设在需要进行无功补偿的各个用电设
备近旁。这种补偿方式能够补偿安装部位以前的所有高、低压线路和电力变压器
的无功功率。对于供电系统中高压侧和低压侧的基本无功功率的补偿,仍宜采用
高压集中补偿和低压集中补偿的方式。
综合考虑上述各种补偿方式,以求经济合理的达到总的无功补偿要求,定采
3.4.3并联电容器的选择计算
(1)无功功率补偿容量的计算Q P(tantan)q P(3-14)用低压集中补偿。
(3)根据车间的需要系数和功率因数参考值表得变电所的COS
1参考值为
0. 65;tan1参考值为1. 17。
(4)无功补偿之后需要达到的功率因数值cos2为0. 9。
(5)qc 为无功补偿率,参考表无功补偿率可得qc 0. 68,需要补偿的容量
Qc=0.68*310=240kvar。 (3-16)
(6)由于在变电所低压侧集中补偿,三相电路因此需要选择台额定电压为6
0. 4 kv、额定容量为40kvar的电容器。通过查询电气手册选出型号为
BZMJ0. 4403的电容器组,金属化膜式低压并联电容器。
第4章短路电流计算
4.1短路电流计算概述
4.1.1短路电流计算的目的
在供、配电系统设计中,为了选用合理的电气主接线,选择限制短路电流的
器件(如电抗器),选用具有足够动稳定度和热稳定度的电气设备,选用载流导
体,设计接地装置,以及设计、整定机电保护装置和自动装置,必须计算短路电
流。
4.1.2短路电流计算的方法和步骤
(一)欧姆法(又名单位法)
1.绘计算电路图,选短路计算点
计算电路图上应将短路计算中需计入的所有电路元件的额定参数都表示出
件有最大可能的短路电流通过。
2. 计算短路回路中各主要元件的阻抗
来,并将各个元件一次编号。短路计算点应选择得使需要进行短路校验的电气元
式中Uc—短路计算点的计算电压,取为比所在电网额定电压高5﹪(单
位为KV),Soc—电力系统出口断路器的断路容量(单位为MVA)
⑵电力线路的阻抗(单位为Ω):
电阻 RWL R0L 电抗 WWL X0L
式中 l—线路长度(单位为km);R0—电路单位长度电阻(单位为Ω/km);
X0—线路单位长度电抗(单位为Ω/km)。
⑶电力变压器的阻抗(单位为Ω):
电阻 | R T | | △ | P | (Uc/Sn) 电抗 | X | | | U | k | % | U | 2 | c | × | 10 | 3 | (4-2) |
| | | k | | | T | | 100 | S | N | | | | | ||||
式中△ | P k | —变压器的短路损耗(负载损耗,单位为W) |
Uk%—变压器的短路电压(阻抗电压)百分值
S | N | —变压器的额定容量(单位为KVA) |
|
U | c | —短路计算点的计算电压(单位为KV) | |
|
3.绘短路回路等效电路,并计算总阻抗
对选定的短路计算点,绘短路回路等效电路。等效电路图上标注的元件阻抗
值必须换算到短路计算点。
电 | 阻 | : | R' | | R | ( | U | ' | 2 | 电 | 抗 | : | X |
| ' | 2 | ||
) | ||||||||||||||||||
| | | | | | | U | c | | | | | | U | c | |
(4-3)
式中R、X—在计算电压为Uc的电网中的电阻和电抗值;
R、X'—换算为计算电压为Uc'的电网中的电阻和电抗值。
4.计算短路电流
分别对各短路计算点计算其三相短路电流周期分量I(3
k)、短暂次暂态短路电
流I'' ( 3 )
、短路稳态电流I(3
)、短路冲击电流i(3
sh)及短路后第一个周期的短路全电流
有效值(又称短路冲击电流有效值)I(3
sh
)
(二)标幺值法(相对单位制法)
1.绘计算电路图,选短路计算点,与前面欧姆法相同。
图4-1 短路计算电路图
2.设定基准容量 | S | d | 和基准电压 | U | d | ,计算短路点基准电流 | I | d | 一般设 | S | d | ||||||||||
=100MVA,设 | U | d | = | U | c | ||||||||||||||||
(短路计算电压)。 |
3.计算短路回路中各主要元件的阻抗标幺值,一般只计算电抗。 (1)电力系统的电抗标幺值
式中 S | oc | Xs*=Sd/Soc | (4-4) |
—电力系统出口断路器的断流容量(单位为MVA)。 |
(2)电力线路的电抗标幺值
XWL*=Xl.Sd/Uc2 (4-5)
式中U—线路所在电网的短路计算电压(单位为KV)
采用标幺值计算时,无论短路计算点在哪里,电抗标幺值均不需换算。
(1)电力变压器的电抗标幺值
XT*=UK%/100.Sd/SN (4-6)
式中U%—变压器的短路电压(阻抗电压)百分值;k
SN—变压器的额定容量(单位为KVA),计算时化为与S同单位。d
采用标幺值法计算时,无论有几个短路计算点,其短路等效电路只有一个。
4.绘短路回路等效电路,并计算总电抗。
在本设计中,我们选择用欧姆法进行短路电流计算。
4.2变压器的各绕组电抗标幺值计算
4.2.1基准值计算
基准容量 | Sj | 100MVA | 230KV |
| |||||||||||||||||||
基准电压: | 220 | KV | U | j | | U | p | | |||||||||||||||
115 | KV | ||||||||||||||||||||||
110 | KV | U j | | U | p | | |||||||||||||||||
37 | KV | ||||||||||||||||||||||
35 | KV | U | i | | U | p | | ||||||||||||||||
基准电流: | I | j | S | j | / | 3 U | j | ||||||||||||||||
220 | KV | 0.251(KA) | |||||||||||||||||||||
110 | KV | 0.502(KA) | |||||||||||||||||||||
35 | KV | 1.56 | (KA) | ||||||||||||||||||||
基准电抗: | Z j | U | j | /S | j | ||||||||||||||||||
220 | KV | 529 ( | | ) | |||||||||||||||||||
|
110KV 132 ()
35KV 13.7 ()
4.2.2各元件参数标幺值计算
三绕组变压器各绕组电抗标幺值计算
Us1%1/2(Us1-2%U s1-3%-Us2-3%)15.25%
Us2%1/2(Us1-2%Us 2-3%-Us1-3%)-0.75%
Us3%1/2(Us1-3%U s2-3%-Us1-2%)7.75%
Xd1*U s1%* S j/100* S n0.127
Xd2
*
-6.25* 10-3
Xd3
*
6.458* 10-2
RT
*
Ps*S j/1000* Sn 24.539* 10-3
GT
*
Po/1000* S j1.63* 10-3
BT
*
Io%* Sn/100 * S j1.44* 10-2
4.3 220KV侧短路计算
220KV 侧短路
X4
X X
0.0179
2
/(2X 2X
X5
)
0.167
0.042
X1 0.127 X 2-6.25
9 2 7
X10X2X80.042375
X110.0212
X12X5X6X110.72
X13X4//X 120.0166
I*1/X1360.213
II*Sj/ 3U l15.113(KA)
4.4 110KV侧短路计算
110KV 侧短路
X 14 | | X | 4 | | X | 6 | | X 11 | | 0.081 |
| |||||
X 15 | | X 14 | //X | 5 | | 0.0546 | ||||||||||
I | * | | 1/X 15 | | 18.318 | |||||||||||
3 | U | l | | 9.197(KA) | ||||||||||||
I | | I | * | S | j / |
4.5 35KV侧短路计算
35KV侧短路
X | AB | | (X 1 | X | 2 | | X | 2 | X | 3 | | X | 1 | X | 3 | )/X | 3 | | 0.1387 |
XAC | -1.433 | ||||||||||||||||||
XBC | 0.0705 |
X16=1/2XAB =0.0694
X 17 | | 1/2 | X | AC | | -0.7165 | ||||||||||||||||||||||||||||||
X 18 | | 1/2 | X | BC | | 0.03525 | ||||||||||||||||||||||||||||||
X 19 | | X 16 | X 17 | /(X 16 | | X | 17 | | X 18 | ) | | 0.0813 | ||||||||||||||||||||||||
X | 20 | | X 16 | X | 18 | /(X 16 | | X | 17 | | X | 18) | | -3.992 | * 10 | -3 | ||||||||||||||||||||
X | 21 | | X | 17 | X 18 | /(X 16 | | X 17 | | X 18 | ) | | 0.0413 | |||||||||||||||||||||||
X | 22 | | X | 4 | | X 19 | | 0.0992 | ||||||||||||||||||||||||||||
X | 23 | | X | 5 | | X | 20 | | 0.163 | |||||||||||||||||||||||||||
X | 24 | | X | 22 | //X | 23 | | 0.0617 | ||||||||||||||||||||||||||||
X | 25 | | X | 24 | X 210.103 | |||||||||||||||||||||||||||||||
I | * | | 1/X | 25 | ||||||||||||||||||||||||||||||||
I | | I | * | S | j | / | ||||||||||||||||||||||||||||||
|
第5章 一次设备的选择与校验
正确选择电气设备是电气主接线和配电装置达到安全、经济运行的重要条件。在进行电器选择时,应根据工程实际情况,在保证安全、可靠的前提下,积极而稳妥地采用新技术,并注意节省投资,选择合适的电气设备。
尽管电力系统中各种电器的作用和工作条件并不一样,具体选择方法也不完全相同,但对它们的基本要求确是一致的。电气设备要可靠地工作,必须按正常工作条件进行选择,并按短路状态来校验动、热稳定性。
本设计中,电气设备的选择包括:断路器和隔离开关的选择,电流、电压互
5.1 断路器和隔离开关的选择感器的选择、避雷器的选择,导线的选择。
的开关电器。
表5-1高压断路器、隔离开关的选择及其校验项目
项目 | 额定电 压 | 额定电流 | 开断电流 | 额定关合电流 | 热稳定 | 动稳定 | |||||||||||||||||||||||||||||
高压断路器 |
|
|
|
|
| 25 i F st 4025 i kV sh | |||||||||||||||||||||||||||||
隔离开关 | ― | ― |
同样,隔离开关的选择校验条件与断路器相同,其型式应根据配电装置的布置特点和使用要求等因素,进行综合技术经济比较后确定。
5.1.1 断路器的选择
1. 断路器的基本结构
1.1 断路器的功能
(1)在正常情况下能开断和关合电路。
(2)在电力系统发生故障时,能将故障从电力系统中切除。
(3)能尽可能的缩短切除故障时间,减轻了电力设备的损坏和提高电力系统
的稳定性。
(4)能配合自动重合闸进行多次关合和断开。
1.2断路器的分类
(1)按照灭弧介质的不同,断路器可分为以下几类。
1)油断路器,又分为多油断路器和少油断路器;2)压缩空气断路器;3)六氟化硫断路器;4)固体产气断路器;5)真空断路器;6)磁吹断路器
(2)按照对地绝缘方式不同,断路器可分为以下几类结构类型。
1)绝缘子支柱型结构;2)罐式型结构;3)全封闭组合结构1.3断路器的选择
220KV侧:
额定电压:220KV
额定电流:I NS/( 3 U N )120MW/( 3 * 220kv)314.92A1600A | |
对断路器进行检验: |
|
动稳定校验:
i | F.st | 一般断路器关合电流不会大于额定动稳态电流,因此,只要 | i | c1 | | i | sh | ,则 | |||
| i | sh | 。故动稳定校验合格。 |
热稳定校验:
短路电流的持续时间,等于继电保护的动作时间(按不利情况,取后备保护
动作时间,设其为1.5s)加上断路器的全开断时间(查资料可得时间为0.06s),
可得:teq1.56s
T3s时,I* (teq/t)15.115* (1.56/3)10.9KAIt40KA所以热稳定
校验合格,选断路器LW-220满足要求
110kV侧:
额定电压:110Kv
额定电流: | I | N | | S/( | 3 U | N | ) | | 120MW/( | 3 | * 110kV) | | 629.83A | | 2000A | ||||||||
短路电流: | IK | | 9.197kA | | 31.5 | kA | |||||||||||||||||
三相短路冲击电流: | i | sh | | 2.55I | p | | 23.452kA | | 80 | kA |
经查表,LW14-110的SF6断路器的技术数据为:
表5-3 LW14-110 的SF6断路器参数
固有分闸时间(ms) | 全开断时间(ms) | 金属短接时间(ms) | (kg) | 额定频率(Hz) | 额定短路闭 |
|
|
|
|
| 100 |
重合闸无电流间隙时间(s) | SF6 气体的分合闸闭锁压力(20℃) | SF6 气体 年漏气量 | 分合闸线圈额定控制电压(V) | 电动机额定电压(V) | 生产厂家 |
0.3 | 4.0 | <1% | DC110/220 | AC380/220 | 西安高压开关厂 |
所以选型号为LW14-110的SF6断路器。
对断路器的校验:
动稳定校验:Ish23.452kAI
dw 80 kA,满足要求。
热稳定校验:teq1.55s (查资料得全开断时间为50ms)
T | 3s | 时, | I | | (teq/t) | | 9.197 | * | (1.55/3) | | 6.61 | kA | 31.5 | kA, | 满足要求。 |
35kA电压级:
额定电压:35kV
额定电流:INS/( 3U N)120MW/(3 * 35 kV)1979.49A
短路电流:Ik15.15kA 16.5kA
三相短路冲击电流:i sh2.55I p38.6325kA1000kA
查表得,35kV系列户外高压少油断路器技术数据中SW2-35型号断路器的
参数如下:
表5-4 SW2-35型号断路器的参数
| ||||||||||||
热稳定校验: | teq | 1.56s | (查资料得全开断时间为0.06s) | |||||||||
Ts | 4s | |||||||||||
I | | (teq/t) | | 9.46 | kA | | 16.5 | kA | ,满足条件。 |
所以选择SW2-35满足要求。
5.1.2.隔离开关的选择
2.1隔离开关用途
隔离开关是一种最简单的高压开关,在实际中俗称闸刀。隔离开关没有专门
的灭弧装置,不能用来开端负荷电流和短路电流。
在配电装置中,其主要用途有:
(1)保证装置中检修工作的安全,在需要检修的部分和其他带电部分,用隔离
开关构成明显的空气绝缘间隔。
(2)在双母线和带旁路母线的主接线中,可利用隔离开关作为操作电器,进行
母线切换或代替出线操作,但此时必须遵守“等电位原则”。
(3)由于隔离开关能通过拉长电弧的方法来灭弧,具有切断小电流的可能性, 所以隔离开关可用于以下操作:
1)断开和接通电压互感器和避雷器。
2)断开和接通母线或直接连接在母线上设备的电容电流。
3)断开和接通励磁电流不超过2A的空载变压器或电容电流。
4)断开和接通变压器中性点接地线(系统中没有接地故障时才能进行)。
2.2隔离开关类型
(1)按绝缘支柱的数目可分为单柱式,双柱式和三柱式三种。
(2)按闸刀的运行方式可分为水平旋转式,垂直旋转式,摆动式和插入式四种。(3)按装设地点可分为户内式和户外式两种。
(4)按是否带接地闸刀可分为有接地闸刀和无接地闸刀两种。
(5)按极数可分为单极式和三极式两种。
(6)按配用操作结构可分为手动,电动和气动三种。
2.3隔离开关选择
220kV侧:
额定电流:
短路电流: IN IK 15.115KA S/( 3 U N314.92A额定电压:220kV
h eq
查表得,型号为GW4-220的隔离开关的技术数据为
表5-5 GW4-220的隔离开关的技术数据
额定 | 额定 | 动稳定电流峰值 | 热稳定电流 | 操动机构型号 | 单项 | 生产厂家 | ||
4s | 5s | 主刀闸 | 接地刀闸 | |||||
220 | 600 | 50 | 14 | 14 | CS14G CJ5、 | CS14G CS14G | 598 | 西安市秦岭电器厂 |
故选型号为GW4-220 的隔离开关
110kV侧:
额定电压:110Kv
额定电流:INS/( 3U N)120MW/( 3* 110kV)629.83A
短路电流:IK9.197kA
三相短路冲击电流:ish2.55Ip23.452kA
动稳定电流Iish23.452kA
热稳定电流IhI (teq/t)9.197* (1.56/4)5.74kA
查表得,型号为GW4-110的隔离开关的技术数据为:
表5-6 GW4-110的隔离开关的技术数据
| ||||||||||||||||||||||||||
额定电压: | 35 | kV | ||||||||||||||||||||||||
额定电流: | I | N | | S/( | 3 U | N | ) | | 120MW/( | 3 | * | 35 | kV) | | 1979.49A | |||||||||||
短路电流: | Ik | 15.15 | kA | |||||||||||||||||||||||
三相短路冲击电流: | i | sh | | 2.55I | p | | 2.55 | * 15.15 | | 38.63kA | ||||||||||||||||
动稳定电流 | I | | i | sh | 38.63kA | |||||||||||||||||||||
热稳定电流 | I | h | | I | | (t | eq | /t) | | 15.15 | * | (1.56/4) | | 9.46 | kA |
查表得,型号为GW4-35的隔离开关的技术数据为:
表5-7 GW4-35的隔离开关的技术数据
额定 | 额定 | 动稳定 | 热稳定 | 操动机构型号 | 单项 | 生产厂家 高清 | |
主刀闸 | 接地刀闸 | ||||||
35 | 2000 | 100 | 40 | CS11G | CS86D | 无水 | 印 |
|
|
| 31.5 | CS17G 、 CJ2-G | CS17G |
| 关厂 |
故选型号为GW4-35的隔离开关。
5.2导体的选择与校验
在稳定周围环境温度下,导体和电气设备长期允许电流Ial应不小于该回路的最大持续工作电流Iw.max,即
Iw.maxIal考虑到发电机、调相机和变压器在电压减低5%时,出力保持不变,
故取其相应回路Iw.max1.05Ial母联QF回路一般可取母线上最大一台发电机或变压器的Iw.max.。
出线回路的Iw.max,除考虑该线路正常运行时的负荷电流外,还应考虑事故时由其他回路转移过来的负荷电流。
220kv 侧:最大持续工作电流: | Iw.max | | 1.05 | * 120/( | 3 | * | 220 ) | | 330.66 | A |
年最大负荷利用小时数为Tmax=6000h,查经济电流密度曲线得经济电流密度为
J=0.9(A/mm2),母线经济截面积为S=I/J=330.66/0.9=367.4mm2..
表5-8 LF21 圆管型铝锰合金导体参数∴选择LF21 圆管型铝锰合金导体作为母线。 |
(1)按最大长期工作电流选择
设当导体在额定环境温度40℃,导体最高允许温度为70℃时,经查表得综合修正系数为K=0.81,则
KIal | | 0.81A | * 1240 | | 1004 . 4 | | 330 . 66 | A |
满足要求。
(1)热稳定校验:
短路持续时间: tk=t后备+t开断=1.5+0.6=1.56s
短路时导体发热量: | Q | K | | I | K | 2T K | | ( 15 . 14 | | 10 | 3 | ) | 2 | | 1 . 56 | | 357 . 58 | | 10 | 6 | J | ||||
导体运行温度为 : | 40 | ) | 2 | 50 . 317 | ℃ | ||||||||||||||||||||
| 70 | | ( | 0 . 81 | | 70 | |
查表得热稳定系数 | C | 95 |
∴满足热稳定要求的导体最小截面积为
S | min | | Q K | |
| | 199 . 05 mm | 2 | | 539 |
C | 95 |
(2)按电晕校验
110kv及以上电压线路发电所母线均应以当地气候条件下晴天不出现全面电晕为控制条件,使导线安装处的最高工作电压小于临界电晕电压
查资料得导线截面大于等于300mm2就不用进行电晕的校验。而所选导线截
面面积为 | 539mm | 300mm | 2 | ,故不用进行电晕校验。 |
110kv侧:
I w . | max | | 1 . 05 | | 120 | | 661 . 33 | A |
|
110kv侧年最大负荷利用小时数为6500h
查经济电流密度曲线得经济电流密度J=0.85A/mm2则母线的经济截面积为:
S | | I w . | max | | 661 . 33 | | 778 . 04 | mm | 2 |
| | J | | 0 . 85 | | | | |
可选择LF21圆管形铝锰合金导体作为母线,其技术数据表如下 表5-9 LF21圆管形铝锰合金导体参数
|
(1)按最大长期工作电流选择
设当该导体在额定环境温度40℃,导体最高允许温度为70℃时,经查表得
综合修正系数为 | K | 0.81 | ,则 | 661 . 33 ( | A ) | |||||
KIal | | 0 . 81 | | 1900 | | 1539 ( | A |
满足要求。
(2)热稳定校验
短 | 路 | 持 | 续 | 时 | 间 | : | tk=t 后 | 备 | +t 开 | 断 | =1.5+0.05=1.55s |
(5-1)
短路时导体发热量: | Q | k | | IK | 2 | t | | ( 9 . 6 | | 10 | 3 | ) | 2 | | 1 . 55 | | 142 . 848 | | 10 | 6 | J | ℃ (5-2) | ||||||
| ( | k | al | 0 | ) | 2 | | 70 | | ( | 0 . 81 | | 70 | | 40 | ) | 2 | | 50 . 317 | |||||||||
导体运行温度为: | | al |
查表可得热稳定系数为C=95
满足热稳定要求的导体最小截面积为
S | min | | Qk | | 142 . 484 | | 10 | 6 | | 125 . 81 ( | mm | 2 | ) | | 594 |
95 | |||||||||||||||
C |
∴满足热稳定要求。
(3)按电晕校验
由于所选导体截面为 | 954mm | 300mm | 2 | ,故不用进行电晕校验。 | |
35kv 侧 | : |
年最大负荷利用小时数Tmax=6500h
按经济电流密度选择导体截面积:正常工作时的最大长期工作电流:
I w | max | | 1 . 05 | | 120 | | 1889 . 51 ( | A ) | (5-3) |
|
查经济电流密度曲线,当Tmax=6500h时,经济电流密度J=0.90A/mm2,
则
Sj=I/J=1889.51/0.90=2099.45(mm2)
查《电力工程电气设备手册-电气一次部分》及《电力工程电气设计手册-
电气一次部分》中表,选取二片 | 125 mm 10 | mm | 矩形硬铝导体并列使用,矩形母 |
线的布置采取截面的长边垂直布置,以提高导体的散热率。相关数据如下:
导体截面S(
集肤效应系数:
mm2):2500;
Kf 1.45导体尺寸b×h(mm×mm):2(125×10);
KIal0. 8131522553. 12 ( A)1889. 51 ( A)
(2)热稳定校验。正常运行时导体温度:
| | | ( | | )I w 2 | max | | 40 | | ( | 70 | | 40 ) | | 1889 . 51 2 | | 56 . 43 | ( | ℃) | , | ||||||
| | 0 | al | |
| al | ) | 2 | | | | | | | | | 2553 . 12 | 2 | | | | | |
(5-4)
查《电力工程电气设计手册》表8—9,得C=91,则满足短路时发热的最小导
体截面为:
S | min | | Q | K | K | f | | 509 . 80 | | 10 | 6 | | 1 . 45 | | 298 . 77 | ( | mm | 2 | ) | | 2500 ( | mm | 2 | ) | , |
C | 91 |
(5-5)
所以满足热稳定要求。
(3)动稳定校验
导体短路时产生的机械应力一般均按三相短路校验。校验应满足的要求为:
xu | | | — | —电气一次部 | |||||||||||||||||
| | ph | | tw | |||||||||||||||||
式中 | — | —短路时导体产生的总机械应力(N | / | cm | 2); | ||||||||||||||||
ph | — | —短路时导体相间产生的最大机械应力(N | / | cm | 2); | ||||||||||||||||
tw | — | —短路时同相导体片间相互作用的机械应力(N | / | cm | 2); | ||||||||||||||||
xu | — | —导体材料的允许应力,其值见《电力工程电气设计手册 | |||||||||||||||||||
分 | 》表8 | | 10。 |
①对于三相导体布置在同一平面的矩形导体,相间应力按下式计算:
| | 17 . 248 | | 10 | | 3 | l | 2 | i | 2 | | |
sh | ||||||||||||
ph | | | | | | | aW | | ||||
式中 l——绝缘子间跨距(cm); a——相间距离(cm); | ||||||||||||
W——导体的截面系数( | cm | 3 | ),见《电力工程电气设计手册——电气一次 |
部分》表8-12及8-13;β——振动系数
相间距离:a0.5m,
冲击电流:ish45. 44 kA
绝缘子的最大允许跨距lmax为:
lmax7
i
.614
sh awxu . 16 ( m )
可见f在35~155Hz范围内,应考虑振动系数,查《供用电工程》表8-14
的曲线,对应f=80.24Hz,β=1.32。
则相间作用应力为:
| | 17 . 248 | | 10 | | 3 | l | 2 | i | 2 | | | 17 . 248 | | 10 | | 3 | | 150 | 2 | | | (45 . 44)2 | | 1 . 32 | ||||||
ph | |
| | aW | | sh | | | | | |
| | 50 | (1 . 44 | | 12 . 5 | 2 | | 1) | | | |||||||||
| 94 ( | N | / | cm | 2 | ) |
②母线同相两条间作用应力计算如下:
当每相为两片时,片间中心距离为a=2b(根据《供用电工程》中描述),则 | ||||||||||||||||||||||
a | | b | | 2 b | | b | | 10 | | | 0 . 074 | , | b | | 10 | | 时,由矩形导体形状系数曲线 | |||||
h | | b | | h | | b | | 125 | | 10 | | | | h | | 125 | 0 . 08 | |||||
得 | K | 12 | 0 . 25 | , | ||||||||||||||||||
f | tw | 2 | 2 . 5 K 12 i sh 2 1 |
据经验一般每隔30~50cm 设一衬垫,所以衬垫跨距可取
Ltw,则短路时
同相导体片间相互作用的应力为:
| | f | tw | 2 | L 2 tw | | 1290 . 50 . 4 | 2 | | 8 . 26 | | 10 | 6 | ( | Pa | ) | | 826 ( | N | / | cm | 2 | ) | | | | (5-6) | ||||||||||||
tw | | 2 | b | 2 | h | | 2 | 0 . 01 2 | | 0 . 125 | | | | | | | / | cm | 2 | | |||||||||||||||||||
所以, | | | ph | | tw | | 94 | | 826 | | 920 ( | N | / | cm | 2 | ) | | xu | | 6860 ( | N | ),满足动稳 |
定校验要求。
综上,所选的二片125mm*10mm矩形硬铝导体满足要求。
第6章二次接线设计
二次回路是指用来控制、指示、监测和保护一次电路运行的电路,亦称二次
系统,包括控制系统、信号系统、监测系统及继电保护和自动化系统等。二
次回路在供电系统中虽是其一次电路的辅助系统,但他对一次电路的安全、可靠、
优质、经济的运行有着十分重要的作用,因此必须予以重视。
枢纽变电所,总容量为60MVA及以上的变电所,装有水冷却或强迫油循环
6.1变电所操作电源选择
如果能够从变电所外引入可靠地380V备用电源。设所用负荷有:主控制室
照明、主建筑物照明和辅助建筑物照明为60KW、锅炉动力、检修间动力、主变
冷却装置动力等为250KW,据以上情况,装设两台所用变压器。
设所用负荷的功率因数为0.9,所用电总负荷:
S所=(60+250)÷0.9=344.44KVA
一台所用变压器故障时另一台可承担70%的负荷,故单台容量为:
SN=0.7×S所=0.7×344.44=241.11KVA
本变电所最低电压等级为35KV,而所用供电等级最高为10KV。故需通过两级电压降落,每级选用两台变压器,最后降为设备的额定电压380/220,查书册选出变压器参数如下:
35KV侧的技术参数如下:
表6-1 35KV 侧的技术参数 |
| (KVA) | 高压 | 低压 | 压(%) | 空载 | 短路 | 流(%) | 标号 |
S7-800/35 | 800 | 38.5 | 10 | 6.5 | 1540 | 11000 | 1.6 | Y,d1 1 |
110KV级侧的技术参数如下:
表6-2110KV 侧的技术参数
型号 | 额定容量(KVA) | 额定电压(KV) | 阻抗电 | 损耗(W) | 空载电 | 连接组标号 | ||
高压 | 低压 | 空载 | 短路 | |||||
S9-315/10 | 315 | 10 | 0.4 | 4 | 700 | 3500 | 1.5 | Y,yn0 |
6.2中央信号装置的选择
6.2.1中央信号装置的设计原则
和预告信号组成。
变电所在控制室或值班室内一般设中央信号装置。中央信号装置由事故信号
并有显示故障性质和地点的指示信号(灯光或信号继电器).
(3)中央事故音响与预告音响应有区别。一般事故音响用电笛,预告音响信号用
电铃。
(4)中央事故与预告信号装置在发出音响信号后,应能手动或自动复归音响,而
灯光或指示信号仍保持,直至处理后故障消除为止。
(5)中央信号装置接线应简单、可靠、对其他电源熔断器应有监视。
6.2.2闪光装置
交流操作多应用于容量小,接线简单的变电所,因此一般不装设闪光装置。
直流操作的闪光装置分为两种,一种由中间继电器和电磁式时间继电器构成,另
一种是由闪光继电器组成。本次设计选取第一种闪光装置。
6.3断路器的控制、信号回路的选择
6.3.1 设计原则
控制、信号回路一般分为控制保护回路、合闸回路、事故信号回路、预告信
号回路、隔离开关与断路器闭锁回路等。
断路器的控制、信息回路电源取决于操作机构的形式和控制电源的种类。断
路器一般采用电磁或弹簧操动机构。弹簧操动机构的控制机构电源也可用直流也
可以用交流,电磁操动机构的控制电源要用直流。
断路器的控制、信号回路接线可采用灯光监视的方式或音响监视方式,工业
企业和民用建筑变、配电所一般采用灯光监视的接线方式。
对断路器的控制、信号回路的接线方式。应能监视电源保护装置(熔断器式
或低压断路器)及跳、合闸回路的完整性。应能指示断路器合闸与跳闸位置状态,
自动合闸或自动跳闸应有明显信号。有防止断路器跳跃(简称防跳)的闭锁装置。
合闸或跳闸后应使命令脉冲自动解除。接线应简单可靠,使用电缆芯数最少。各
断路器应有事故跳闸信号,事故跳闸信号使用使中央信号装置发出音响及灯光信
号,用灯光表示本回路发生事故,并用信号继电器直接指示故障性质。当断路器
转换开关采用LW12,LW2型时,要求将红灯也接入闪光回路,使闪光信号起作用。
转换开关在”预跳”位置时红光闪光,转换开关在(预合)位置时绿光闪光。对于
有可能出现不正常情况的线路或回路,应装有预告信号。预告信号应能使中央信
线路及回路。 |
6.3.2变压器的电压回路与电流回路
(1)测量表计电流回路,如图6-1。
图6-1测量表计电流回路
(2)差动保护电流回路,如图6-2。
图6-3过电流过负荷保护电流回路
(4)测量表计电压回路,如图6-4
图6-4测量表计电压回路
6.3.3变压器二次接线图
如图6-5。
图6-5变压器二次接线图
图6-5变压器二次接线图
二次接线图元件标注PA1—交流电流表,42L20—A□/5A型;PW1—有功
功率表,42L20-W型、100V/5A;PJ1-最高需量电能表,DZ9型、100V/5A;
PJR1—三相无功电能表,DX865型,110V/6A;KD1~KD3—差动继电器;
DCD-2A型;KA1~KA4—电流继电器,DL-21/□型;KM1、KM3—中间继电器,
DZB-284型,110V/□A;KM2—中间继电器,DZY-206型、110V;KT1、KT2—
时间继电器,DS-32/2型,110V;KT3—时间继电器,SS-94/22型,110V;
KS1、KS4—信息继电器,DX-31B/□A型;KS2、KS3—信号继电器,DX-31B型,
K22-20×2A型,110V;
型,110V红、绿、白;FU1~FU8—熔断器, HR1、HR2,HG1、HG2,HW1、HW2—信号灯,K22-DPRT14-6A型;R1、R2—电阻,ZG11-500.075A;SA1、SA2—转换开关, SAR1、SAR2主令开关,
连接片
第7章防雷接地
变电站的电气设备在运行中可能会出现过电压,过电压主要有雷电过电压和
由于误操作产生的内部过电压两种类型。究其分类,可以归类为以前几种:雷电
过电压分为直击雷过电压、感应雷过电压和入侵波过电压;内部过电压包括工频
电压(操作电容负荷过电压、操作电感负荷过电压、解裂过电压和间歇电弧过电
压)。
过电压(长线电容效应、不对称接地故障以及甩负荷)、谐振过电压以及操作过
变电所应装设直击雷保护装置的设施
(1)屋外配电装置,包括组合导线和母线廊道;
(2)油处理室、燃油泵房、露天油罐及其架空管道、装设油台、大型变压器
修理间、易燃材料仓库等建筑物;
(3)雷电活动特殊强烈地区的主厂房、主控制室和高压屋内配电装置室。
(一)对主厂房设置直击雷保护:
1.装设避雷针及避雷网
变配电所及其屋外装置,应装设避雷针及防护直击雷。如果变配电所及其屋
外装置处在相邻构筑物防雷保护之内时,可不再装设避雷针或避雷网。
避雷针宜设独立的接地装置。在非高土壤电阻率地区,其工频接地电阻
R≤10Ω。当有困难时,可将接地装置与主接地网连接,但避雷针与主接地网的地
下连接点至35KV及以下设备与主接地网的地下连接点之间,沿接地线的长度不
得小于15m。
2.装设避雷线
处于峡谷地区的变配电所可利用避雷线来防护直击雷。
35KV及以上的变配电所架空进线上,假设1~2km的避雷线,以消除近区
进线上的雷击闪络,避免其引起的雷电入侵波对变配电所电气装置的危害。
3.装设集中接地装置
应用扁钢将所有避雷针水平连接起来,并与厂房内钢筋焊接成一体,在适当
地方接引下线,且应与总接地网连接,并在连接处加装集中接地装置,其工频接
地电阻不大于10Ω。设备接地点应远离避雷针接地引下线的入地点,避雷针接地
引下线应远离电气设备。
(二)主控制室及室内配电装置直击雷保护措施:
(1)若有金属屋顶或屋顶上有金属结构时,将金属部分接地;
(2)屋顶为钢筋混泥土结构,将其钢筋焊接成网接地。
本设计中采用220KV、110KV配电装置构架上装设避雷针,35KV屋内配
电装置上装设独立避雷针进行直接保护,钢筋混泥土结构焊接成网并接地,为了
防止反击,主变构架上不设置避雷针。
对变电所必须进行防雷保护的对象及措施见下表
建筑物及构筑物名称 |
| 防雷措施 | |
| 钢筋混泥土结构 | 避雷针。当在架构上装设避雷针时,可将架构支柱主钢筋作引下线接地,作引下线的钢筋不少于2 根 | |
屋外安装的变压器 |
| 装设独立避雷针 | |
屋外组合导线及母线桥 |
| 装设独立避雷针;在不能装设独立避雷针时,考虑在附近主厂房屋顶装设避雷针 | |
主控制楼(室) | 金属结构 | 金属架构接地 | 但在雷电活动特殊强烈地区应设独立避载高清 |
钢筋混泥土结构 | 钢筋焊接成网并接地 | ||
屋内配电装置 | 钢筋混泥土结构 | 钢筋焊接成网下 并接地 无 |
变压器检修间 | 钢筋混泥土结构 | 钢筋焊接成网接地 |
7.1.2变电站防入侵雷保护
雷电波侵入:雷电不直接放电在建筑和设备本身,而是对布放在建筑物外部
的线缆放电。线缆上的雷电波或过电压几乎以光速沿着电缆线路扩散,侵入并危
及室内电子设备和自动化控制等各个系统。
输电线路一般主要考虑防反击,绕击。
反击:雷击杆塔时因雷电流通过杆塔和接地体,使杆塔电位升高,在相导线
上产生感应过电压,如果升高塔体电位和相导线感应过电压造成的电位差超过线
路绝缘闪络电压值,就会发生闪络,这种闪络称反击闪络简称反击。
绕击:雷电绕过避雷线保护角击在架空相线上,产生过电压,导致线路过压
保护跳闸。
清楚了送电线路雷击跳闸的发生原因,我们就可以有针对性的对送电线路所
经过的不同地段,不同地理位置的杆塔采取相应的防雷措施。
1.防直击、绕击,就是使输电线路不受雷直击,措施是沿线路装设避雷线或
避雷针;
缘、降低杆塔的接地电阻;
2.防闪络,就是使输电线路受雷后绝缘不发生反击闪络,措施是加强线路绝
动重合闸等
7.1.3避雷器的选择
1、磁吹阀式避雷器的电气参数如下:
(1)额定电压Ube:避雷器的额定电压应与其安装地点系统的额定电压等级
相同。
(2)灭弧电压Umi:对35kV及以下的中性点不接地系统,灭弧电压取为最
高工作线电压的100%~110%;对110kV及以上的中性点直接接地系统,灭弧
电压取为系统最大工作线电压的80%。
(3)工频放电电压Ugf:指在工频电压作用下,避雷器发生放电的电压值。
在中性点绝缘或经阻抗接地的电网中,工频放电电压一般大于最大运行相电压的
3.5倍;在中性点直接接地的电网中,工频放电电压应大于最大运行相电压的3
倍。工频放电电压应大于灭弧电压的1.8 倍。
(4)残压Ubc:按 | U | bc | | 2 . 35 | | 2 | | U | mi | 计算来确定。 |
(5)冲击放电电压Uchfs:我国生产的避雷器其冲击放电电压与5kA 的残
压基本相同。
2、避雷器的选择与校验
(1)220KV侧避雷器的选择与校验
①型式的选择:根据规程及本设计,选用FCZ系列磁吹阀式避雷器。
②额定电压的选择: | U | bc | | U | N | net | | 220 | kV |
因此选FCZ-220避雷器,其参数如下表7-2所示。③灭弧电压校验:
最高工作电压: | U | max | | 1 . 15 U | N | | net | | 252 | kV | ,满足要求。 | |||||||||
| 200 | kV | ||||||||||||||||||
直接接地: | U | mi | | c | d | U | max | | 0 . 8 | | 252 |
表7-2避雷器参数
| |||||||||||||||||
⑥冲击放电电压校验: | U | chfs | | 0 . 95 U | bc | | 0 . 95 | | 664 | | 630 ( | kV | ) | | 710 | kV | ,满足 |
要求。
综上,所选FCZ-220型避雷器满足要求
(2)110KV侧避雷器的选择和校验
①型式的选择
根据规程及本设计,选用FCZ系列磁吹阀式避雷器。
②额定电压的选择:
U | bc | | U | N | net | | 110 | kV |
因此选FCZ-110避雷器,其参数如下表7-3所示。③灭弧电压校验:
最高工作电压: | U | U | max | dU | |
直接接地: | mi | ||||
| c |
型号 | 额定电压(kV) | 灭弧电压
(kV) | 工频放电电压有效值 (kV) | 冲击放电电峰
不大于(kV) |
残压不大于 (kV) | |||||||||||
不小于 | 不大于 | |||||||||||||||
FCZ-110 | 110 | 126 | 255 | 290 | 345 | 365 |
④工频放电电压校验:
下限值: | U | gfx | | 255 | kV | | K | 0 | U | xg | | 3 | | 126 | | 218 kV | ||||
3 | ||||||||||||||||||||
上限值: | U | gfs | | 1 . 2 U | gfx | | 1 . 2 | | 218 | | 261 ( | kV | ) | <290kV |
上、下限值均满足要求。
⑤残压校验: | U | bc | | 2 . 35 | | 2 | | U | mi | | 2 . 35 | | 2 | | 100 . 8 | | 334(kV)365KV | , |
满足要求。
⑥冲击放电电压校验: | U | chfs | | 0 . 95 U | bc | | 0 . 95 | | 334 | | 317(kV)345KV | ,满足 |
要求。
综上,所选FCZ-110型避雷器满足要求。
(3)35KV 侧避雷器的选择和校验 |
型号 | 额定电压(kV) | 灭弧电压有效值(kV) | 工频放电电压有效值(kV) | 冲击放电电
不大于(kV) |
残压不大于 (kV) | ||||||||
不小于 | 不大于 | ||||||||||||
FZ-35 | 35 | 41 | 82 | 98 | 134 | 134 |
③灭弧电压校验:
最高工作电压: | U | max | | 1 . 15 U | N | net | | 1 . 15 | | 35 | | 40 . 25(kV) | |||||||
非直接接地: | U | 40 . 25 kV | ,满足要求。 | ||||||||||||||||
mi | | c | d | U | max | | 1 . 0 | | 40 . 25 | |
④工频放电电压校验:
下限值: | U | gfx | | 82 | kV | | K | 0 U | xg | | 3 . 5 | | 40 . 25 | | 81(kV) | ||||||||||||
| |||||||||||||||||||||||||||
上限值: | U | gfs | | 1 . 2 U | gfx | | 1 . 2 | | 81 | | 97 | ( | kV | ) | <98KV, | ||||||||||||
上、下限值均满足要求。 | |||||||||||||||||||||||||||
| 2 | | 40 . 25 | <134KV, | |||||||||||||||||||||||
⑤残压校验: | U | bc | | 2 . 35 | | 2 | | U | mi | | 2 . 35 |
满足要求。
⑥冲击放电电压校验: | U | chfs | | 0 . 95 U | bc | | 0 . 95 | | 133 . 7 | | 127(kV)<134KV,满 |
足要求。
综上,所选FZ-35型避雷器满足要求。
7.1.4变压器的防雷保护
三绕组变压器在正常运行时,可能出现只有高、中压绕组工作而低压绕组开
路的情况。这时,当高压或低压侧有雷电波作用时,因处于开路状态的低压侧对
地电容较小,低压绕组上的静电分量可达很高的数值以致危及低压绕组的绝缘。
为了限制这种过电压,需在低压绕组出线端装一组避雷器,但若在低压绕组接有
25m以上金属外皮电缆时,因对地电容增大,足以限制静电感应过电压,故可不
必再装避雷器。
主变压器220kV、110kV侧中性点是直接接地,因而需在中性点装设雷电过
电压保护装置,选用金属氧化物避雷器。35kV侧中性点是非有效接地,其中性
点采用全绝缘,运行经验表明不加保护时的故障率很低,故一般不需保护。
所用变压器高、低压侧均需装设阀式避雷器避雷器。
1.内部过电压:
由于操作、事故或其他原因引起系统的状态发生突然变化将出现从一种稳定
7.1.5内部过电压及其保护
过电压。
发生的称为操作过电压,其持续时间一般在几十毫秒之内;在暂态过渡过程结束
以后出现的,持续时间大于0.1s甚至数小时的持续性电压称为暂时过电压。暂
时过电压又可以分为工频过电压和谐振过电压。
2.限制措施:
在中性点装消弧线圈可以避免因电弧接地而引起的过电压;改善电网的参数
或者运行方式避免谐振条件的形成;保证断路器三相同期动作,不重燃,或在断
路器触头处装低值并联电阻,降低操作过电压;装设并联电抗器补偿线路的电容
效应,限制切合空载线路时的过电压;改善发电机的调速装置降低甩负荷引起的
过电压;使用性能优良的避雷器限制过电压。本设计主变压器220kV、110kV侧
采用中性点直接接地的方式,这样单相接地将会造成很大的单相短路电流,断路
器将立即跳闸而切断故障,经过一段短时间歇,让故障点电弧熄灭后再自动合闸,
如能成功,可立即恢复送电;如不能成功,断路器将再次跳闸,不会出现断续电
弧现象,可限制电弧接地过电压。
7.2 接地装置设计
7.2.1接地简介
为保证电工设备正常工作和人身安全而采取的一种用电安全措施。接地通过
金属导线与接地装置连接来实现。接地装置将电工设备和其他生产设备上可能产
生的漏电流、静电荷以及雷电电流等引入地下,从而避免人身触电和可能发生的
火灾、爆炸等事故。
接地装置由接地体和接地线组成。直接与土壤接触的金属导体称为接地体。
电工设备需接地点与接地体连接的金属导体称为接地线。接地体可分为自然接地
体和人工接地体两类。自然接地体有:①埋在地下的自来水管及其他金属管道
(液体燃料和易燃、易爆气体的管道除外);②金属井管;③建筑物和构筑物与大
地接触的或水下的金属结构;④建筑物的钢筋混凝土基础等。人工接地体可用
垂直埋置的角钢、圆钢或钢管,以及水平埋置的圆钢、扁钢等。当土壤有强烈腐
蚀性时,应将接地体表面镀锡或热镀锌,并适当加大截面。水平接地体一般可用
直径为8~10毫米的圆钢。垂直接地体的钢管长度一般为2~3米,钢管外径为
35~50毫米,角钢尺寸一般为40×40×4或50×50×4毫米。人工接地体的顶端应
接地电阻稳定,且不易遭受外力破坏。
常用的接地有保护接地,工作接地,防雷接地,屏蔽接地,防静电接地等。 而在变埋入地表面下0.5~1.5米处。这个深度以下,土壤电导率受季节影响变动较小,
雷电引向自身,雷电流经过其引下线和接地装置进入大地。变电站中的接地装置
可以减小接地电阻,从而降低雷电流或短路电流通过时其上的电位升高,同时还
可以均衡地面电位分布、降低接触电位差和跨电位差的作用
7.2.2接地网型式选择
220kv及以下变电站地网网格布置采用长孔网或方孔网,接地带布置按经验
设计,水平接地带间距通常为5m~8m。除了在避雷针(线)和避雷器需加强分
流处装设垂直接地极外,在地网周边和水平接地带交叉点设置2.5m~3m的垂直
接地极,进所大门口设帽檐式均压带,接地网结构是水平地网与垂直接地极相结
合的复合式地网。
长孔与方孔地网网格布置尺寸按经验确定,因为接地网边缘部分的导体散流大约是中心
部分的3~4倍。因此,地网边缘部分的电场强度比中心部分高,电位梯度较大,整个地网
的电位分布不均匀。接地钢材用量多,经济性差。在220kV及以下的变电工程中采用长孔
网或方孔网,因为入地故障电流相对较小,地网面积不大,缺点不太突出。
总结
本设计为220kV变电所设计,是在完成本专业所有课程后进行的综合能力
考核。通过对原始资料的分析、主接线的选择及比较、短路电流的计算、主要电
器设备的选择及校验、线路图的绘制以及避雷器针高度的选择等步骤、最终确定
了220kV变电站所需的主要电器设备、主接线图以及变电站防雷保护方案。通
过本次毕业设计,达到了巩固理论知识,掌握变电站电气部分和防雷保护设计的
基本方法,体验和巩固我们所学的专业基础和专业知识的水平和能力,培养我们
问题的能力的目的。
算以及各种电力手册及其电力专业工具书的使用,务求使我们更加熟悉电气主接线,掌握变电站电气部分和防雷保电力系统的潮流及短路计运用所学知识去分析和解决与本专业相关的实际问题,培养我们独立分析和解决
参考文献
[1]耿建风.智能变电站设计与应用[M].中国电力出版社。2012
[2]高翔,张沛超.数字化变电站的主要特征和关键技术[J].电网技术.2006年12 月,第30卷第23期.
[3]沈键,黄晓峰,高贵旺,徐石明,丁杰,黄国方.数字化变电站的关键技术 [J].江苏电机工程.2007年8月,第26卷增刊.
[4]德]Klaus-PeterBrand,[德]VolkerLohmann,[德]WolfgangWimmer.变电站自动化 [M].中国电力出版社,2009.
[5]吴皓.数字化变电站设计简述[J].企业科技与发展.2009年第14期.
[7] 刘介才.工厂供电设计指导第2版[M].机械工业出版社.2011 技术论坛论文集.
[6]隆丽,王国海.浅谈数字化变电站的基础技术[J].输变电技术,2007年云南电力
中国电力出版社.2011
[11]刘学军.工厂供电设计指导[M].中国电力出版社。2008
[12]程逢科.电器二次回路识图400例[M]。中国电力出版社.2013
[13]王世政.电力工程类专题课程设计与毕业设计指导教程[M].中国水利水电出版
社.2007
[14]水利电力部西北电力设计院.电力工程电气设计手册电气一次部分[M].中国
电力出版社,1989
[15]应敏华,程乃蕾,常美生.供用电工程[M].中国电力出版社,2006.9
[16]卓乐友. 电力工程电气设计200例[M].中国电力出版社,2004
[17]宋继成. 220~500kV变电所电气主接线设计[M].中国电力出版社,2004
[18]苏小林,阎晓霞.电力系统分析[M].中国电力出版社,2007
[19]李光琦. 电力系统暂态分析[M].3 版.中国电力出版社,2007
[20]西安交通大学.短路电流实用计算法[M].中国电力出版社,1982
[21]电力工业部西北电力设计院.电力工程电气设备手册电气一次部分上、下册 [M].北京:中国电力出版社,1998
[22]黄伟,付艮秀.电能计量技术[M].2版.中国电力出版社,2007
[23]常美生,张小兰.高电压技术[M].中国电力出版社,2006.11
[24]谷水清,李凤荣.电力系统继电保护[M].中国电力出版社,2005
[25]王玉华,赵志英.工厂供配电[M].中国林业出版社.2006
[26]刘涳.常见低压电器与可编程程序控制器[M].西安电子科技大学出版社.2005[27]谈世哲.ProtelDXP 2004电路设计基础[M].机械工业出版社.2010
[28]刘天琪,电力系统分析理论(第二版)[M].科学出版社.2012
[28]马永翔.电力系统继电保护(第2版)[M].北京大学出版社.2013
[29]张沛超,高翔.数字化变电站系统结构[J].电网技术.2006年12月,第30卷第 24期.
致谢
毕业设计的这段时间是我学生生涯中最有价值的一段时光。这里有治学严谨而不失亲切的老师,有互相帮助的同学,更有向上、融洽的学校生活氛围。借此论文之际,我想向所有人表示我的谢意。
首先感谢我的指导老师。本论文是在老师的指导下和同学们的帮助下修改完成的。在此,我要向他们的细心帮助和指导表示由衷的感谢。在这段时间里,我 更感受到他们工作中的兢兢业业,生活从他们身上不仅学到了许多的专业知识,
中的平易近人。此外,他们严谨的治学态度和忘我的工作精神值得我去学习。
非常感谢大家在我的毕业设计中,给予我极大的帮助,使我对整个毕业设计 使我有了很大的收的思路有了总体的把握,并耐心的帮我解决了许多实际问题,
获。同时,他们在整个开发过程中提出了许多建设性意见,并给我解决了一些专
同时感谢所有关心帮助过我的同学、老师和学校。感谢多年来传授我知识的老师们,更要感谢那些对我学习上支持和鼓励的人。业性问题。